Legacy code
Legacy description
New code
New description
Action
Code conventions
- Charset
- Uppercase A–Z, digits, space, hyphen, ampersand. No leading or trailing spaces.
- Length
- Longest code is 18 characters — well inside the ~50 character EAM field.
- Style
- Mnemonic alpha, matching the supplier commodity draft (
VLV GATE,GT BLADE). - Structure
- Flat list with a readable prefix. The group gives a one-level rollup for spend and inventory reporting without a second EAM field.
- Catch-alls
- Every family ends in a
… PARTS OTHERcode so nothing is left blank. A catch-all that keeps growing needs a new code.
Scope & assumptions
- Perspective: owner/operator. Codes describe what the stations buy and stock, not what an OEM builds.
- In scope: gas turbine, steam turbine, HRSG, diesel and recip gensets, dual-fuel backup, balance of plant, T&D and substation, plus all general workplace purchases.
- Out of scope: hydro, wind, solar, nuclear.
PS97(Nuclear) is flagged for retirement. - Services excluded — those stay in the supplier commodity list. The one exception is
MISC SERVICE ITEM, for non-stock expense lines sitting on part records today. - No standards mapping (UNSPSC, NAICS, eCl@ss) was requested, so none is applied. A column can be added later.
- No part master export was available, so the list is built from the two source files plus standard station storeroom categories.
Found in the supplier draft
- Duplicate code.
CATERING SVCSappears twice. Row 33 is described as “Cabling – Communications” — wrong code pasted. SuggestCABLE COMM SVCS. - Duplicate code.
VIBRA CTRL BALappears twice, for Monitoring and Balancing. SuggestVIBRA CTRL MONandVIBRA CTRL BAL. - Truncated code.
COMP(Computer Field Device Maintenance) has no suffix. SuggestCOMP FIELD MNT. - Typo.
FILERS REPAIRis described as “Filers – Repair Maintenance”. Should readFILTERS REPAIR/ Filters. - Length outliers.
PIPING INSTALL REPand a few others run 17–18 characters while the rest cap at 16. Harmless if the field allows it, but worth standardizing.
Next steps
- Review the code list and mark anything to add, merge or rename.
- Confirm the 21 retirements on the crosswalk tab.
- Send a part master export (part number, description, UOM, vendor) for bulk auto-assignment by keyword — that is where the 68 catch-all mappings get resolved.
- Name the governance owner: who approves new codes, and how requests are submitted.
Prefix legend
557 codes across 45 groups · 233 legacy EAM commodities crosswalked